Highly efficient, easy-to-deploy 20kW, 400V 3-phase uninterruptible power supply (UPS) that brings best-in-class power protection to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Compact design, high-density technology and modular architecture keep total cost of ownership low and operational efficiency at the highest levels. Galaxy VS reduces your energy losses by up to 66% with the patented ECOnversion mode – reaching up to 99% efficiency levels and delivering more energy savings than even our industry-leading 97% efficiency in normal operating mode. The UPS is EcoStruxure-ready to give you peace of mind with cloud-based remote monitoring and management via your smartphone. Includes 5x8 start-up service. For battery runtime details, see the runtime charts published under the Documents tab.
Includes: Dust filter, Installation guide, Integrated network management, Power modules ship installed, Start-Up Service, Top and bottom cable entry
Key features
UPS topology: Double-conversion (Online)
Output power capacity: 20 kVA
Output power: 20000 W
Waveform: Sine
Input operation voltage (min): 340 V
Input operation voltage (max): 460 V
Input frequency: 40/70 Hz
Output operation voltage (min): 380 V
Output operation voltage (max): 415 V
Output frequency: 50/60 Hz
Maximum current: 37 A
Number of input phases: 3
Number of output phases: 3
Efficiency: 96.9%
Input power factor: 0.99
Crest factor: 2.5:1
Output voltage Total Harmonic Distortion (THD): 3%
Noise level: 65 dB
Audible alarm(s): Yes
Audible alarm modes: Alarm when on battery, Low battery alarm, Overload alarm
AC outlet types: Hard Wire 5-wire (3PH + N + G)
SmartSlot: Yes
SmartConnect port: No
Form factor: Tower
Specifications
Design
Form factor
Tower
Product colour
White
Display type
LCD
LED indicators
Yes
International Protection (IP) code
IP21
Features
UPS topology
Double-conversion (Online)
Output power capacity
20 kVA
Output power
20000 W
Waveform
Sine
Input operation voltage (min)
340 V
Input operation voltage (max)
460 V
Input frequency
40/70 Hz
Output operation voltage (min)
380 V
Output operation voltage (max)
415 V
Output frequency
50/60 Hz
Maximum current
37 A
Number of input phases
3
Number of output phases
3
Efficiency
96.9%
Input power factor
0.99
Crest factor
2.5:1
Output voltage Total Harmonic Distortion (THD)
3%
Noise level
65 dB
Audible alarm(s)
Yes
Audible alarm modes
Alarm when on battery, Low battery alarm, Overload alarm
Certificates
Certification
CSA C22.2 NO. 107.3, EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, FCC Part 15 Class A, IEC 60721-4-2 Level 2M2, UL 1778 5th edition